STLMIN
Safety and maintenance panels for industrial gas supply systems - STLMIN
DRUVATEC LOW - FLOW RANGE - MINIMAL - VERSION
for industrial, inert, flammable, oxidizing gases and gas mixtures. Not usable for corrosive or toxic gases and gas mixtures.
SPECIAL FEATURES:
On a Safety and Maintenance Panel, both safety-related components and maintenance-related systems of a central, industrial gas supply are combined.
SAFETY RELATED COMPONENTS:
- safety device with multiple functions for flammable, oxidizing gases
- safety relief valve designed and adjusted based on worst case scenario measurements of DruvaTEC Low Flow manifold regulators
- pressure indication port for monitoring of pipeline pressure, gauges are exchangeable without disassembly of the panel
PANEL CONSISTS OF TWO PLATES
- Easy installation of ground plate without weight of complete safety and maintenance panel
- Simple hang front plate including safety and maintenance panel
- Fixing front plate by only one bolt
TECHNICAL DATA
Nominal working pressure rates: | 10; 20; 40 bar |
Maximal allowable working pressure: | 11,5; 22; 53 bar |
Nominal flow rate: | 20 m3/h (at 20 bar) |
Test after production: |
100% functionality 100% seat leakage test 100% pressure test |