REDUZIERSTATION MM40 - STABILIZER
Produktgruppencode: 3611Whole medical range is available on
Manifold MM40 – STABILIZER is a second stage pressure reduction unit with the task to equalize the eventual pressure variation in the hospital pipeline system to ensure a correct pressure from the terminal units.
MM40 – STABILIZER is only second stage reduction unit where the primary gas supply is provided by high pressure gas manifolds (such as MM40 – HP Unit). In case of signal for pressure deviation in relation to the alarm settings, the alarm can easily be displayed on a Gas alarm unit. It is also possible to send information to the central operation control.
The stabilizer can be delivered with either pressure transmitter 4–20 mA, pressure transmitter 0–50 mV or with pressure switches. Gas reduction unit MM40 – STABILIZER must always be installed in compliance with the standards
EN ISO 7396-1 and the appropriate national standards.
FOR A COMPLETE MM40 STABILIZER MANIFOLD ADD:
- Plastic cover for locking
- Alarm unit (included if ordered together with HP unit)
Item No. | Denomination | Gas | PRV | Alarms |
0727329 | MM40 – Stabilizer | O2, N2O, Air, CO2, N2 | – | – |
0727337 | MM40 - Stabilizer | AIR-800 | – | – |
0727332 | MM40 - Stabilizer | O2, N2O, Air, CO2, N2 | With pull-ring | Pressure switch |
0727344 | MM40 - Stabilizer | O2, N2O, Air, CO2, N2 | With pull-ring | 4-20 mA |
0727343 | MM40 - Stabilizer | O2 | – | – |
0727346 | MM40 - Stabilizer | Air | – | – |
0727347 | MM40 - Stabilizer | Air-800 | – | – |
0727348 | MM40 - Stabilizer | CO2 | – | – |
0727364 | MM40 - Stabilizer | N2O | – | – |
ACCESSORIES
Item No. | Denomination |
COM001002 | Locable cover |
735100000796 MM40 Stabilizer leaflet EN
TECHNICAL DATA
Gases: | O2, Air, Air-800, N2, N2O, CO2, (all medical gases) |
Nominal flow: | 40 m3h |
Inlet maximal pressure: | 16 bar |
Outlet nominal pressure: | 4,5 bar (setting range 0,5 – 10 bar) |
Inlet connection 1: | G1/2"M + soldering piece pipe ∅ 12 mm |
Inlet connection 2: | Optional (G1/2"M + soldering piece pipe ∅ 12 mm) |
Outlet connection: | G1/2"M + soldering piece pipe ∅ 12 mm |
Pressure relieve valve: | Optional (6,8 bar; outlet pipe ∅ 15 mm) |
Pressure sensors: | Optional (Pressure switches; Transmitters 0–50 mV; 4–20 mA) |
Emergency QC inlet: | Optional QC by national standards |
Regulatory status: |
Complies with Medical Devices Directive 93/42/EEC Complies with EN ISO 7396-1 (Central Gas Supply Systems) Complies with EN 60601-1-2 (Electromagnetic compatibility) present SIS HB 370 and HTM 02-01 |